You are not logged in. Would you like to log in now?
Login NowGEMC-FW-32CNVKT | 32 Zone Conventional Commercial Fire Alarm Panel Kit, 24 Volt Panel
32-Point, 2 NAC Circuit With 4A, Red Enclosure, Built-In Horn/Strobe Synch, Dual DACT, 2-Serial Port
Brand:
Napco
Product Code:
GEMC-FW-32CNVKT
Categories:
Fire Systems
Share:
Features
- Includes Menu-Driven Fire Keypad, Mounts Anywhere on Bus
- (8) 2-Wire Fire Input Zone, Expandable to 32 via Conventional Addressable and/or Wireless
- 14x16 Heavy Duty Red Enclosure
- GEMC-PS24V4A-R 4Amp, 24V Power Supply
- GEMC-F8ZCPIM Conventional 8-zone 2-wire fire input module
- GEMC-FK1 Red LCD Fire Keypad
Specifications
System
- Main Control board supports up to (2) Addressable SLCs (addressable Signaling Line Circuit controllers)
- Fire 4-wire bus for keypads and non-SLC (conventional) devices, including 12V devices
- Power Supply includes either 4A or 7A @ 24V
- RS-232 Printer Module for optional onsite parallel printer
- Supports up to 7 fire keypads, GEMC-FK1, mounted anywhere on the bus
- Easy-to-use Gemini-style menu-driven operation with backlit custom alphanumeric display and functionality for Reset, Acknowledge, Silence (with disable)
- Synch module built in on each NAC (System Sensor & Wheelock protocols)
- Full Keyswitch Support
- Synch module built in on each NAC (System Sensor & Wheelock protocols)
- Dual Phone Line built in
- 2 On board serial ports - one for internet reporting; one for high-speed local downloading
- TCP/IP Internet reporting module
- Regulated Auxiliary Power Supply - Commercial fire, 12V regulated 2A
- Addressable SLC Loop Isolator (optional use - for some fire applications requiring increased circuit integrity, e.g., meets Class A, Style 7 loop requirements
- Medium Enclosure – supports 16 AH at 24V
- Dimensions: 16”x 14.25” x 5.2” (H x W x D) without cover (*Note: Only 1 SLC is accomodated) 16Ah battery backup capacity
Inputs
- Addressable SLC Loop – supports up to (2) 126 point loops
- Commercial RF Receiver
- Supports Commercial Wireless Fire devices
- Wireless Smoke Detector
- Wireless Heat Detector
- Wireless contact transmitter (for waterflow, tamper, pull stations, etc.) Model GEMC-WL-WD2
- Conventional 1- to 4-zone EZM Expansion modules on the 4-wire fire bus or SLC loops
- Conventional 2-wire or 4-wire smoke detector input module
- SLC Fire Devices Supported
- Analog Smoke Detector
- Analog Heat Detector
- Duct Detector
- Pull Station
- Conventional Zone Module
- Short Circuit Isolator
Outputs
- Four on board Class B or 2 Class A NAC circuits, 2 amps each, total 6.5 amps at 24V
- Built in Wheelock and System Sensor NAC sync/strobe/horn protocol allows initial silence of audible appliances while maintaining visual notification, without the use of additional modules
- Addressable SLC Fire Devices: Supervised relay, unsupervised relay
- Fire 4-wire bus devices: 8 zone form C relay (GEMC-RM3008), 8 open collector output (GEMC-OUT8)
Advantages
- Easy Wire Compatibility - Addressable SLC controller supports shielded, unshielded, twisted and untwisted wire - ideal for retrofits
- Longer SLC loop lengths, support more device loads each, too: 10,000 ft #14AWG ,6,200 ft #16AWG, 4,000 ft, #18AWG
- Support for Legacy and Existing Notification Appliances -One NAC output configurable for 12V for easy retrofit compatibility
- UL Regulated NAC outputs
- Automatic drift compensation for smoke detectors
- Keypads mount anywhere on the bus and have flash-able firmware – for updates via Quickloader command
- Programmable obscuration level by smoke detector device
- Smoke Obscuration Report genererated remotely or locally or in any of 3 ways - Quickloader device sensitivity report allows the printout of a report for the AHJ listing the current status of all smoke detectors in the system including the programmed obscuration level and the actual sensitivity reading for each device. This report can be generated remotely (uploaded) or locally through notebook PC or use optional onsite printer
- Full line of UL Commercial Devices for more flexibility & labor-savings
- Separate 7Amp 4-NAC Extender, 4 onboard NACs with up to 2A ea., expandable for up to 24 per system. Up to 28Ah total battery capacity. Regulated 24V Aux. power. Monitors AC, battery trouble, tamper and ground fault on Napco bus
Agencies
- NFPA 72, UL Commercial Fire, UL864 9th Ed., UL985, CSFM and NYC Fire Department Certifications
Data Sheet
Cut-Sheet
User Manual
Manual